a7b8a53bb8a68330ebb618058fffd847项目安全隐患识别口袋书 ——机电安装项目 中建三局二公司安装公司 2021 年 6 月 项目安全隐患识别口袋书目录 第一章:施工用电························································· 1 第二章:高处作业·····························································15 第三章:施工消防····························································· 33 第四章:施工机具····························································· 45 第五章:起重吊装····························································· 58 第六章:文明施工································································· 69 第七章:其他································································· 75 第一章:施工用电 序号 常见隐患类别 危险等级 序号 常见隐患类别 危险等级 1 电源线拖地、泡水,未绝缘悬挂 A 级 10 配电箱缺少线路图 C 级 配电箱电工未每日巡检,缺少巡检 2 电缆线敷设无保护措施 A 级 11 B 级 记录表或巡检滞后 3 电源线胶皮破损未绝缘包扎 A 级 12 配电箱内接线一闸多机 A 级 4 违规使用两芯线、花线 A 级 13 配电箱接线端子无防护和线路标识 B 级 5 违规使用多项插头、家用插板 A 级 14 用电设备接线时未接 PE 线 A 级 配电箱无箱门、箱门与箱体未做跨 6 非电工接电(未持证上岗) A 级 15 A 级 接 配电箱内有杂物,或配电箱周边堆 7 用电设备与开关箱距离超过 3m A 级 16 B 级 放较多杂物 8 配电箱未可视化验收 C 级 17 用电设备直接接二级箱用电 A 级 用电设备接入漏保上端,未经过漏 9 配电箱内元器件歪斜和松动 B 级 18 A 级 电保护器 1 问题描述:①现场临时用电使用的电源线拖地、泡 整改措施:①制作加工绝缘挂钩支架,对拖地电源 水。 线进行绝缘悬挂处理。 原因分析:①现场临电交底不到位,施工过程中巡 管控措施:①临电施工前,进行专项交底,要求劳 查不到位 务队进场时加工制作。 2 问题描述:①电缆线敷设过路无保护。 整改措施:①在非过路要求电缆线沿地面敷设须订 方木盒保护,并刷警示油漆;②对无条件架空或埋地 时,可采用带线槽减速带对电缆进行保护。 原因分析:①作业人员安全意识低;②检查不全面, 管控措施:①加强临电使用危害类教育;②对现场临 责任单位未对临电隐患引起足够重视。 电安全进行全面排查,加强日常管理;③制定合理的 防护方案并交底到位。 3 问题描述:①使用两芯线;②电源线接头处未绝缘 整改措施:①淘汰两芯线,采用合格的三芯线并规 包扎。 范接线;②对接头处电源线采用绝缘胶带包扎。 原因分析:①分包单位无专业电工;②项目对劳务 管控措施:①要求劳务单位配备专职电工;②加强 分包临时用电交底、验收不到位。 对劳务分包临时用电的交底和验收工作巡查力度;③ 对不合格电缆及时清退出场。 4